factory control panel
Power General panel

Summary

HXGN15-12L  HV switchgear metal enclosed AC ring main unit is a new HV  apparatus which introduced from abroad and accord with the requirement of rural distribution and city distribution in nation. Main switch, operation mechanism and component use the SFL-12 model  SF6 switch equipment  produced by ABB company or FLN36-12D model SF6 switch equipment produced by our company. Also can use the HAD/US model SF6 circuit breaker or VD4-S model vacuum circuit breaker produced by company ABB according to requirement of customer operation type is manual and motor.

Ambient condition

  • Environmental air temperature: -40℃ ~ +40℃; 2 Altitude  ≤ 1500m;
  • Ambient humidity: monthly mean relative humidity≤90% ,daily mean relative humidity≤95%;
  • Saturated vapor pressure: daily mean relative humidity≤2.2 × 10-3MPa, monthly mean relative humidity≤1.8×10-3MPa;
  • The earthquake intensity is not exceeding 8 degree.
  • Installation  site: without  fire  risk,  explosion hazard, heavy pollution,  chemical  corrosion  and violent vibration;

Model

factory control panel
Power General panel

Technical specification

No. ItemUnitTechnical parameters
V unitC unitF unitD unit
1Rated voltagekV12
2Rated frequencyHz50
3Rated currentA630630125630
4Rated short circuit breaking currentkA20 31.5 
5Rated short circuit making currentkA505080 
6Rated    transfer currentkA  1.7 
7Rated    earth fault breaking currentA 30  
  8Ratedshort-time withstandcurrent    & durationMain loop (4S)  kA2020 20
Earthing    switch    &ground loop (2S)2020 20
Ground loop (2S)17.417.3 17.3
  9 Rated peak withstandcurrentMain loop  kA5050 50
Earthing    switch    &ground loop5050 50
Ground loop43.543.3 17.3
   10 Insulationtest(fracture   /earthing)1min P.F withstand voltage (fracture/earthing) kV 48/42
Lightning (fracture   (peak) kV 85/75
11Main loop resistanceμ Ω<120<120<550<50
12Mechanical lifetime100001000010000 
13Working air pressureMP0.02-0.04
14Protection  grade:  enclosure  /  air tank IP4X/IP67
15Outline dimension(W×D×H)mm425×797 × 1473425×797 × 1473425×850 × 1473425×797 × 1473

Main Structure

1. It has the characteristics of compact structure, safe and reliable, long life, maintenance free;

2. All the live parts are insulation package, non exposed parts, avoid to discharge between phases;

3.  The  product  is  all-insulation,  all-shielding,  maintenance  free  structure  without  external pollutants and metal lap effect;

4. Modular assembly design, easy for circuit expansion, unit replacement and scheme changes;

5.  The  product  is  equipped  with  spring  operating  mechanism,  with  the  functions  of manual operation, electric operation, reserve distribution automation interface.

Installation Dimension

The construction of the installation foundation shall comply with the relevant provisions in the ‘Technical Specifications for Construction & Acceptance of Power Construction ’. The equipment unit is at least 1000mm above the wall surface. The installation basic dimensions as shown below.


 

factory control panel
Power General panel
LoopWDH
3loop+PT+meter cabient2525  1200      2400
4loop+PT+meter cabient2900
5loop+PT+meter cabient3275
6loop+PT+meter cabient3650
3 loop+PT1780  1050
4 loop+PT2105
5 loop+PT2430
6 loop+PT2755
3 loop (manual)1425  1050  1880
4 loop (manual)1800
5 loop (manual)2175
6 loop (manual)2550

Note: The above data is for reference only, unit mm

factory control panel