Summary
applied to the 3.6KV~12kV three phaseAC 50/60Hz system toreceive anddistribution power energy,and suitable for continually operation andrebuilding the switchgear which install oil switch.The busbar is single busbarsystem and double busbar subsection system.
XGN2-12(G)is suitable for high altitude area which is developed on base ofgeneral switch.
Theswitchgear conforms to GB3906″3~35KVAC Metal-enclosed Switchgear”and IEC62271-200 standard,and with function of five protections locking.The mainswitch of panel is ZN28A-12 series vacuum drcuit breaker,equip withCD10 series and CD17 electromagnefism,CT8,CT17/CT19series spring operating mechanism.
Ambient condition
- Ambient temperature: -25℃ ~+40℃;
- Altitude: ≤1000m, high altitude type: ≤3000m;
- Relative humidity: daily average ≤ 95%, monthly average ≤ 90%;
- Vapour pressure: daily average ≤ 2.2X10Mpa, monthly average ≤1.8X10Mpa;
- Earthquake intensity:≤ 8 degree;
- Applicable occasions should be free from inflammable, explosives and severe vibration.
Model

Product feature
XGN2-12 series fixed AC metal enclosed switchgear (short for panel as below) is a new product designed and developed byHEAG, based on the introduction of advanced foreign design and manufacturing technology. It applies to 3.6~12kV three phaseAC 50Hz single busbar or single busbar sectional transport, distribution system, as for receiving and distributing power energy, and realize to control, monitor and protect power circuit. It is widely used for power plant, substation, petroleum,metallurgy, chemical, natural gas and other civil field.
Structure feature:
1.XGN2-12 series is metal enclosed fixed switchgear, the body is welded with angle steel and steel board, inner and outer coating is solid by static spray plastic powder.
2.This panel conforms to GB3906 3-35kV AC Metal enclosed switchgear and international standard IEC62271-200 besides, prevent from opening and closing connecting switch with load, prevent from opening and closing c ircuit breaker, prevent from entering into interval with electricity, prevent from closing earthing switch with electricity (five protections adopt simple, reliable mechanical interlock device). The power indicator is installed in front of panel which reflect voltage in the side of circuit. When circuit side with electricity, lock the enclosed board and panel door.
3.Same type product and structure component can exchange each other.
4. Enclosure
4.1 The inner structure of panel is divided into circuit breaker compartment, busbar compartment, cable compartment,relay compartment, use steel plate to separate panels. Use eddy current steel plate and epoxy resin busbar bushing to separate panel.
4.2 The panel adopts cold roll steel sheet and angle steel to weld together, without reticulation fabric, non-flame-resisting materials. Outer insulating creeping distance of components and supporting insulator, pure porcelain insulation≥ 1.8cm/kV, organic insulation ≥ 2.0cm/kV.The air distance of phase to phase, phase to earth ≥ 125mm. There is an intelligent hygrothermoscope to start or stop heater according to the humiture condition of circuit breaker compartment and cable compartment in panel, Prevent from forming moist and high temperature.
4.3 There is a viewing port for observing of closed and open position of upper, down connecting switch without open the door. The panel is double maintenance, inspect relay compartment equipments, operating mechanism, mechanical interlock and transmission part in front, inspect main busbar, shunt circuit busbar, cable terminal, connecting switch and earthing switch.
4.5 Circuit breaker: The circuit breaker is located in the middle part, disconnecting switch and earthing switch and interlock mechanism are above it, and with indicator device, describe open and closed position.
4.6 Transformer: CT is mounted on the underpart of front side, connect with circuit breaker and connecting switch, main loop without electricity. It can carry out preventive test, inspection and exchange, the secondary wire of CT to earth reliably .
4.7 Disconnect switch and earthing switch: connecting switch, disconnect switch and earthing switch ca n be seen through viewing port, controlled by a set of manual operating mechanism to assure of program and reliable locking for circuit breaker, disconnect switch and earthing switch, meet the requirement of five protection.
4.8 Measuring instrument, relay protection, monitor device and auxiliary circuit.
4.9 Earthing: It takes a consideration of 4 × 40mm2 copper busbar as earthing body along with whole width of all panel extending.
Technical specification
1. Primary wiring scheme to see table 1, primary wiring scheme combination to see table 2;
2. If used for high altitude, choose high altitude components, such as ZN28A-12GD;
3. Technical specification of panel to see table 3;
4. Technical specification of circuit breaker and operating mechanism:
No . | Item | Unit | Data | ||||||
1 | Rated voltage | kV | 11 | ||||||
2 | Highest voltage | kV | 12 | ||||||
3 | Rated current | A | 630 | 1000 | 1000 | 1250 | 2000 | 2500 | 3150 |
4 | Rated short circuit breaking current | kA | 20 | 31.5 | 40 | ||||
5 | Rated short time withstand current(4s) | kA | 20 | 31.5 | 40 | ||||
6 | Rated peak withstand current | kA | 50 | 80 | 100 | ||||
7 | Rated short circuit making current(peak) | kA | 50 | 80 | 100 | ||||
8 | Protection degree | IP2X | |||||||
9 | Operating type | Electromagnet type, spring charging type | |||||||
10 | Outline dimension(width × depth × height) | mm | 1100×1200×2650 |
1. Rated current of plateau altitude switchgear: 630/1000/1250A
2.Outline dimension of plateau altitude switchgear: 1200 × 1350 × 2900mm
Item | Unit | ZN28A-12/1000-20 | ZN28A-12/ 2000— 31..5 | ZN28A-12/ | 2500-403150-40 | ||||
Rated voltage | kV | 10 | |||||||
Highest voltage | kV | 12 | |||||||
Rated frequency | Hz | 50 | |||||||
Rated current | A | 1000 | 1250,2000 | 2500,3150 | |||||
Rated short circuit breaking current | kA | 20 | 31.5 | 40 | |||||
Rated short circuit making peak current | kA | 50 | 80 | 100 | |||||
Rated short time withstand current | kA | 20 | 31.5 | 40 | |||||
Rated peak withstand current | kA | 50 | 80 | 100 | |||||
Rated short time withstand current duration | s | 4 | |||||||
Mechanical endurance | Times | 1000 | |||||||
Rated STC breaking times | Times | 30(50) | |||||||
Vacuum Interrupter vacuum degree | Pa | ≤ 6.6X10-2 | |||||||
Arcing time | ms | ≤ 20 | |||||||
Type | CD10 I CD10 Il CD10 l | ||||||||
Workingvoltage(V) | Open coil | 110 , 220 | |||||||
Open coil | 24,48,110,220 | ||||||||
Workingcurrent(A) | Close | 110 | 196 240 294 | ||||||
220 | 98 120 147 | ||||||||
Close | 24 | 37 | |||||||
48 | 18.5 | ||||||||
110 | 5 | ||||||||
220 | 2.5 | ||||||||
CT8- CTB- Il | |||||||||
Workingvoltage(V) | Storage motor | ||||||||
Shunt trip | -48 , | ||||||||
No-voltage trip | ~110(110) , ~220 | ||||||||
Storage time | s | 必 5 | |||||||
Over current trip | A | 5 | |||||||
Opening time | s | DC electromagnetism | |||||||
Opening time |
Outline and dimension

Drawing 1a XGN2-12-07D Outline Drawing
1.Busbar compartment 2.Pressure release channel 3.Metering compartment
4.Combination switch compartment 5.Manual operating and interlock mechanism
6.Main switch compartment 7.Electromagnet or spring mechanism
8.Earthing busbar 9.Cable compartment

Drawing 1b XGN2-12(G) Basic Reference Drawing
1.Busbar compartment 2.Pressure release channel 3.Small busbar compartment
4.Metering compartment 5.Transfer switch compartment
6.Disconnect switch operating and interlock mechanism
7.Circuit breaker compartment 8.Circuit breaker operating mechanism
9.Earthing busbar 10.Cable compartment 11.Overhead inlet-outlet extra panel 12.Busbar bushing