Summary
KYN28C-7.2/12(J.R)/31.5-40 armoured movable AC metal-clad switchgear (short for F-C circuit panel) is refer to distribution device applies to 3.6~12kV, rated frequency 50/60Hz power system. Large rated short circuit breaking current underrated current, Widely used for electrical power, chemical and generate electricity department, etc. Flexible configure, convenient operation, security and reliability, the performance conforms to GB3906-91, IEC62271-200 standard. It applies to 120 0 kW and below power factor motor or 1600 kVA or below transformer for control and protection.
Standard
GB/T11022 | The Common Technical Clauses of HV Switchgear and Controlgear Standard |
IEC62271 & GB3906 | 3~35kV AC Metal Enclosed Switchgear |
GB 3309 | The Mechanical Test of HV Switchgear at Normal Temperature |
GB 311.1 | Insulation Configuration of HV Distribution Equipment |
GB/T16927.1 | First Part in HV Test Technology: General Test |
GB 15166.2 | AC HV Fuse, Limited Current Fuse |
GB/T14808 | AC HV Contactor and Motor Starter |
Ambient condition
- Ambient temperature: -15℃ ~+40℃ , daily average: ≤ 35℃;
- Altitude: ≤1000m;
- Relative humidity: daily average ≤ 95%, monthly average ≤ 90%;
- Earthquake intensity:≤ 8 degree;
- Occasions without flammable and explosive matter, without corrosive chemical and frequent severe vibration.
Model

Structure feature
1. The enclosure and each compartment are separated by metal sheet. The enclosure and dummy plate are made of aluminium-zinc plated steel. Associate with KYN28-12 abreast to design many kinds of sche mes for distribution device according to usage. It can use with KYN96-12 parallel according to requirement.
2. Assembly structure: The enclosure is completely made of aluminium-zinc plate steel sheet after processed by CNC machine and multi-bending, then is assembled with bolts. So it has strong mechanical strength and guarantee the neatness and good appearance. Cubicle door is through plastic spray treatment to ensure good anti-impact and corrosion-proof ability.3. Panel is combination type, without welding, without deformation, miniaturization volume. With reliable “five protection” interlock function, compulsive mechanical interlock on rear and front door.
3. Vacuum contactor and fuse are mounted on handcart, central drawout type, action of pulling and pushing depend on
lead screw, low operation strength, convenient to exchange , there is guideway in the handcart compartment.
4. Busbar compartment are used for installation busbar. Main busbar gets across busbar insulating bushing to isolate the neighboring panel busbar compartment. Main virtue for desig n is limiting the accident and prevent from spreading to other area when breakout emergency in busbar compartment.
5. Allowed CT, earthing switch, lightning arrester, heater and cable to mount in cable compartment. Equip with slotting and knock-down non metal sealed board and stainless steel.
6. Allowed relays, instruments, signal light and operating switch to mount in relay compartment. It can install small busbar compartment on the top of relay compartment according to user requirement, capacity for covering fifteen control busbar.
7. The protection of enclosure is IP4X, even if open the door, the protection class also reach IP2X, It can prevent huma n and outside solid from approaching living part and moving components.
8. It is normal operation when repair any compartment except main busbar compartment .
9. There is a channel on the top of circuit breaker compartment, busbar compartment, cable compartment. When occur emergency relative to circuit breaker, main busbar and cable compartment and appear arc, the gas pressure in panel will not go up until reach utmost, then metal board open automatically to release gas pressure and assure of security for human and equipments.
10. There is a secure and reliable mechanical interlock device to meet five protection in the panel. 1.1.Prevent from drawing out and plugging in primary isolating contact with electric charges.
1.2.Prevent from making contactor (or circuit breaker) when close earthing switch.
1.3.Prevent from making earthing switch with electricity when handcart is on working position. 1.4.Prevent from entering into living separation.
1.5.Prevent from fault open and close contactor( or circuit breaker).
11. Equip with earthing conductor inside panel to connect whole line panel. Panel frame, door, cover board, moving curtain board and circuit breaker handcart frame all connect with earthing conductor.
12. The air clearance between electrified body or electrified to earth is not less than 100 mm, The air clearance between electrified body and insulating components inside composite insulation is not less than 30mm.
13. It need not exchange main busbar when this product combine with KYN 28 series circuit breaker panel, isolating panel, PT panel and measurement panel, it can run through directly.
14. SMC or DMC insulating material.
Technical specification
F-C Panel technical specification
Item | Unit | Data | ||
Rated voltage | kV | 7.2 | 12 | |
Rated frequency | Hz | 50/60 | 50/60 | |
1min P.F. Withstand voltage | Phase to phase, phase to earth | kV | 32 | 42 |
Across open contacts | kV | 36 | 48 | |
Lightning impulse withstand voltage | Phase to phase, phase to earth | kV | 60(peak) | 75(peak) |
Across open contacts | kV | 70(peak) | 85(peak) | |
Main busbar | Rated current | A | 630~4000 | |
4s rated short time withstand current | kA | 40 | ||
Rated peak withstand current | kA | 100(peak) | ||
F-C | Rated current | A | 315 | |
Rated short time withstand current | kA | 40 | ||
Rated peak withstand current | kA | 100 | ||
Max join current | kA | 3.2 | ||
Rated short circuit breaking current | kA | 40 | ||
Rated short circuit making current | kA | 100 | ||
Outline dimension(W | mm | 650 × 1500(1300,1670) | ||
Protection degree | IP4X(open handcart compartment door: IP2X) |
Technical Specification for AC Vacuum Contactor
Item | Unit | Data | ||
V7C(ABB) | JCZ | |||
Rated voltage | kV | 7.2/12 | 7.2/12 | |
Rated current | A | 400 | 400 | |
Max rated breaking current | A | 5000 | 3200 | |
Rated short time withstand current 4s | A | 5000 | 5000 | |
Max peak withstand current | kA | 55(1/21 cycle) | ||
Rated making current | A | 5000(100 time) | 5000 | |
Mechanical endurance | Mechanical holding | 10,000 time | 25 | 10 |
Electric holding | 100 | 100 | ||
Natural closing time | ms | 60~90 | 100 | |
Natural opening time | ms | 15~30 | 35 | |
Rated operating voltage | V |
Outline and dimension

1.Metering compartment door
2.Handcart compartment door
3.Propulsion mechanism hole
4.Cable compartment door
5.Earthing switch operating hole
6.Lightning arrester
7.Heater
8.Current transformer
9.Earthing switch
10.Down contact box
11.Upper contact box
12.Main busbar compartment
13.Branch busbar
14.Main busbar
15.Pressure release board
16.Small busbar compartment
17.Metering compartment
18.Aerial plug
19.Limited current fuse
20.Vacuum contactor handcart
21.Trolley
22.Sensor
23.Cable compartment