factory control panel
Power General panel

Summary

KYH3-12s removable ac double-busbar metal-clad switchgear (switchgear for short hereunder)  apply to 3.6kV~12 kV three-phase AC 50Hz power system, as a control and protection device  of the load of the dual power radiation type electric supply system and use cables, overhead lines, transformers and capacitors as load. The switchgear conforms to GB3906、IEC60694, and with  perfect and reliable anti misoperation function.

Technical specification

No.ItemUnitData
1Rated voltagekV12
2Rated currentA1250
3Rated frequencyHz50
4Rated peak withstand currentkA80
5Rated short-time withstand currentkA31.5
6Duration of rated short circuit withstand currents4
7Rated short circuit breaking currentkA31.5
8Rated short circuit making currentkA80
  9 Rated insulation level1min P.F.  Withstand  kVphase to phase, phase to ground / isolating fracture:42/49
lightning impulse withstand voltagephase to phase, phase to ground / isolating fracture:75/85
 10Voltage ofsubsidiarycontrol circuitrated voltageVDC:220/110 ,AC:220/110
1min P.F.  WithstandV2000
11Protection grade Enclosure:IP4X;open door:IP2X
12Outline dimension(W×D×H)mm800×2260×2300
13Weightkg1000  ~1500

Main Structure

1. With the functions of distribution, metering, compensation, measurement and control, etc.;

2. Response timely and quickly, the compensation effect is good, reliable work, also can according to user s ’ requirements to add the leakage protector;

3. Automatic operation function: recloser;

4. Improve the power factor of the power grid.

Basic Structure

factory control panel
Power General panel

1. circuit breaker      2. flexible door mechanism      3.lower contact box       4.CB chamber

5. upper contact box      6. secondary air socket       7. isolation interlock chamber

8. meter chamber      9.small busbar chamber     10. pressure releasing pathway of CB chamber 11.busbar chamber    

 12.disconnector chamber      13. disconnector     14. busbar chamber

15. isolation chamber      16. pressure releasing pathway of cable chamber      17. disconnector

18.current transformer      19.earthing switch       20. cable chamber      21. cable clamp

factory control panel
Power General panel
factory control panel
Power General panel
WDNote
800 2200 Cable inlet-outlet line
1000
800 2400 Overhead inlet-outlet line
1000