factory control panel
Power General panel

Summary

KGH1-40.5 Fixed AC Metal-clad Switchgear is designed and developed on XGN17  switchgear. It  conforms with GB3906, GB/T 11022, DL/T 593 and other standards and relevant requirements of this kind of product.

Ambient condition

  • Environmental air temperature:upper limit is +40℃ , the mean value in 24h is no more than 35 ℃ , lower limit is -25℃;
  • Altitude  ≤ 1000m;
  • Relative  humidity:  daily  average  value    ≤  95%, monthly average value  ≤ 90%;
  • Vapor pressure: daily mean relative humidity ≤2.2kPa, monthly mean relative humidity≤1.8kPa;
  • Earthquake intensity: not exceeding 8 degree;
  • Installation  site: without  fire  risk,  explosion hazard, heavy pollution,  chemical  corrosion  and violent vibration

Model

factory control panel
Power General panel

Technical specification

No.ItemUnitTechnical parameters
1Rated voltagekV40.5
2Rated currentA630 ,1250 ,2000 ,2500
3Rated frequencyHz50
4Rated peak withstand currentkA50 ,63 ,80
5Rated short-time withstand current20 ,25 ,31.5
6Duration of rated short-circuit withstand currents4
7Rated short circuit breaking currentkA20 ,25 ,31.5
8Rated short circuit making current50 ,63 ,80
  9 Ratedinsulation level 1min P.F. Withstand Voltage  kVPhase to phase, phase to   ground/ isolating fracture:95/118
Lightning    impulse    withstandvoltagePhase to phase, phase to   ground/ isolating fracture:185/215
 10Voltage     of auxiliarycontrol loop1min P.F. Withstand Voltage DC220/110, AC220/110
Lightning    impulse    withstandvoltage2000
11Outline dimension(W×D×H) 1818×3200×3200
12Rated operation sequence O-0.3s-CO-180s-CO
13Loss category for running continuity LSC2B

Main Structure

1. It adopts integrated solid structure design, and the product has beautiful appearance;

2. The product is completely formed by Al-Zn coated steel plate after multiple bending processed, It has the characteristics of high precision, strong rigidity and good corrosion resistance;

3. Equipped with ZN12-40.5 vacuum circuit breaker that has reliable performance;

4. The normal operation of the switchgear, including opening and closing of breaker switch and the upper and lower disconnector, can be carried out under the closing condition of the high voltage compartment door is open;

5.  Conventional  relay  protection  or  integrated  microprocessor-based  protection  device  can  be configured. Wall bushing used for internal pressure outside the shielding structure, avoid discharge local high field, effective suppression of solid insulation thermal breakdown and electrochemical breakdown in AC battery under the action, so as to improve the life of insulation, anti aging effect.

Basic Structure

A.LV instrument compartment            B. CB compartment

C. Busbar compartment                      D. Cable compartment

1. Releasing plate of the CB compartment      2. The upper disconnector       3.Bushing

4. Branch busbar assembly      5. Releasing plate of the Busbar compartment

6. Releasing plate of the Cable compartment      7. Insulator       8. Power cable

9. Earthingt busbar assembly      10. Cable clamp       11. The tower sealing ring

12. The lower disconnector      13. Actuating linkage       14.Current transformer

15. Vacuum circuit breaker      16.Operation mechanism