GENERAL AND APPLICATION
KYH1-40.5 model Metalclad Centered Metal-enclosed Switchgear (hereinafter referred to as switchgear) is a new product independently designed and developed by HEAG group after absorbing international advanced technology. The product has the outstanding advantages as follows:
1.1 The enclosure is completely formed by Al-Zn coated steel plate after multiple bending processed by CNC machine, then is assembled with the bolts, which has strong mechanical strength and effectively ensure the neatness and good appearance. The door is painted by the plastic powder and has strong anti-impact and corrosion proof ability. The protection grade of enclosure is IP4X.
1.2 The main circuit breaker is VHY1-40.5 model Solid-sealed Vacuum Circuit Breaker, which is independently designed and developed by HEAG group. It has the unique advantages of long life, high reliability, less maintenance and small volume, furthermore, it has perfect and reliable anti-misoperation function. Of course, the switchgear can be equipped with other similar circuit breakers.
1.3 The circuit breaker handcart is centred structure, which inherits the advantage of KYN28 model switchgear. This structure avoids the adverse effects for the installation foundation against the movable/fixed contacts, and is convenient for maintenance and overhaul.
The switchgear applies to three phase power system of rated voltage 24 40.5kV AC 50Hz(or 60Hz) for receiving and distributing power energy, and also for circuit control , monitor and protection. It can be used in single-busbar system and single-busbar section system.
It accords with the standards as follows:
IEC 62271 -200 <Alternative-current Metal-enclosed Switchgear and Control Equipments of rated voltage 3.6 40.5kV>;
IEC 62271-1 <High-voltage switchgear and controlgear – Part 1: Common specifications>;
GB 3906 <Alternative-current Metal-enclosed Switchgear and Control Equipments of rated voltage 3.6 40.5kV>;
GB/T 11022 <General Technology Requirements of High-voltage Switchgear and Control Equipments>;
GB/T 1984 <High-voltage Alternating-current Circuit Breaker>;
GB/T 1985 <High-voltage Alternating-current Circuit Breaker and Earth Switch>;
DL/T 404 <Alternative-current Metal-enclosed Switchgear and Control Equipments of rated voltage 1 52kV>;
DL/T 593 <General Technology Requirements of High-voltage Switchgear and Control Equipments>.
NORMAL SERVICE CONDITIONS
- Environmental ambient temperature: +40℃ ~ -15
, daily average not exceed 35
;
- Altitude above sea level: not exceed 1000m;
- Relative humidity: daily average less than 95%, monthly average less than 90%;
- Saturated vapor pressure: daily average less than 2.2
10-3MPa, monthly average less than 1.8
10-3MPa ;
- Earthquake intensity: not exceed 8 grade;
- The environmental air without flammable, explosive and corrosive material;
- Site without frequent vibration.
If the service conditions exceed the above mentioned range, the user shall consult the manufacturer.
The switchgear shall be equipped with a heater to avoid the condensation. The heater shall operate all daywhen the switchgear is in the steady or operating state.
For the special locations of bad operation conditions, e.g . the underground substation, the unmanned substation and son on, the constant temperature & humidity-reduced equipment shall be added indoor to improve the operating condition and ensure the safe and reliable operation of the switchgear.
NORMAL SERVICE CONDITIONS

MAIN TECHNICAL PARAMETERS
4.1 Main technical parameters of switchgear
Item | Unit | Data | |
Rated voltage | kV | 40.5 | |
Ratedinsulation level | 1 min P.F. withstand voltage | kV | Interphase, phaseto ground95; betweengaps 118 |
Lightning impulse withstand voltage | kV | Interphase,phase toground 185;between gaps215 | |
Rated frequency | Hz | 50 (or 60) | |
Rated current | A | 630, 1250, 1600, 2000, 2500 | |
Rated short-time withstand current(4s) | kA | 25, 31.5 | |
Rated peak withstand current ※ | kA | 63, 80 | |
IAC grade | BFLR | ||
Kind of operation continuity | LSC2B-PM | ||
Protection grade | IP4X(enclosure), IP2X(compartment) | ||
Outline dimension (W | mm | 1200 | |
Weight | kg | < 1600 |
- The short-circuit capacity of CT shall be separately considered;
- If installed with Lightening Arrester or the aerial busbar outgoing/incoming, the cubicle depth shall be 2800mm. 4.2 Main technical parameters of VHY1-40.5 model indoor vacuum circuit breaker
4.2 Main technical parameters of VHY1-40.5 model indoor vacuum circuit breaker
Item | Unit | Data | |
Rated voltage | kV | 40.5 | |
Rated | 1 min P.F. withstand voltage | kV | Interphase and phase to ground 95 |
insulation level | Lightning impulse withstand voltage | kV | Interphase and phase to ground 185 |
Rated frequency | Hz | 50 (or 60) | |
Rated current | A | 630, 1250, 1600, 2000, 2500 | |
Rated symmetrical short-circuit breaking current | kA | 25, 31.5 | |
Rated peak withstand current | kA | 63, 80 | |
Rated short-time withstand current(4s) | kA | 25, 31.5 | |
Rated operating sequence | O-0.3s-CO-180s-CO | ||
Opening time | ms | 20~50 | |
Mechanical life | time | 20000 | |
Electrical life | grade | E2 | |
Rated out of phase earth fault breaking current | kA | 27.3 | |
Rated cable charging breaking current | A | 50 | |
Rated voltage/current of opening operation | V/A | DC(AC)220/1.5, DC(AC)110/3 | |
Rated voltage/current of closing operation | DC(AC)220 /1.5, DC(AC)110/3 | ||
Rated instantaneous over-current tripping current | A | 5 | |
Rated voltage of secondary circuit | DC(AC)220, DC(AC)110 | ||
Rated voltage of motor for energy storage | V | DC(AC)220, DC(AC)110 | |
Rated output power of motor for energy storage | W | 70 | |
Time of energy storage | s | ≤ 12 |
4.3 Main technical parameters of JN model earth switch
Item | Unit | Data |
Rated voltage | kV | 40.5 |
Rated P.F. withstand voltage(1 min) | 95 | |
Rated lightening impulse withstand voltage(peak value) | 185 | |
Interphase centre distance | mm | 280 |
Rated short-time withstand current(4s) | kA | 31.5 |
Rated short-circuit making current | 80 | |
Rated peak withstand current | 80 |
STRUCTURE FEATURES
5.1 Integrative three-dimensional structural design and good appearance;
5.2 The enclosure is made of imported Al-Zn coated plate after double bending and assembled with the bolts. It has the features of high accuracy, good rigidity and good corrosion-proof function;
5.3 Adopt a new-style APG contact box with the interphase insulation baffle plate inside the cubicle;
5.4 Adopt electric field grading voltage and shielding design, which is of reliable insulation and can satisfy full-working condition requirements.
5.5 Be provided with a mature and reliable five-prevention locking device to completely realize the closed-door operation
In front of the cubicle.
5.6 Be provided with the reliable VHY1 model solid-sealed centred vacuum circuit breaker and JN model earth switch with short-circuit making ability and a quick closing mechanism. Meanwhile, the location of the handcart is obviously up, and the coordination between the guide rail and the bottom board machine adopts multi-point(up down left right) positioning mode, which can effectively decrease the electric power torque arm between the movable contact and the fixed contact, greatly enhance the ability of anti active thermal stable current.
5.7 The circuit breaker handcart is centred structure, which inherits the advantage of KYN28 model switchgear. This structure avoids the adverse effects for the installation foundation against the movable/fixed contacts, and is convenient for maintenance and overhaul.
5.8 Be equipped with normal relay protection device or integrated micro-computer protection relay.
5.9 The fixed contact box and through bushings are of inner grading voltage & outer shielding structure, which can avoid the partial point discharge, effectively restrain the thermal breakdown and the electric thermal breakdown of the solid insulation under AC electric field, so as to improve the actual effect of insulation life and insulation aging protection.
PRODUCT STRUCTURE
The product structure shown as Fig. 1.
The switchgear consists of a fixed body and the withdrawable parts. According to the function, the fixed body can be divided into four function units of busbar compartment, CB compartment, cable compartment and LV compartment. The mounting screws for side mounting is of special design, which will make the cubicles without the exposed fastening pieces at the side, and is convenient to put them together. If the faults occur, the cubicles can be quickly pulled out from the cubicle arrangement so as to recover power supply in time.
The withdrawable parts includes the circuit breaker, the lightening arrester, the fuse, the disconnector and potential transformer.
The power indicator is mounted in the cubicle for inspecting the operating condition of primary circuit and is user-selectable which consists of a HV sensor and a display. The sensor is mounted at the side of busbar or feeder, and the display is mounted on the name plate of the L.V. Compartment.
6.1 Enclosure, baffle plate and pressure releasing device
The enclosure and the baffle plates are made of Al-Zn coated steel plate after processed by CNC machine and double -bending, then are assembled with the bolts of high strength, and three pieces of double-layer double-bending pillars(8mm thick) are in the middle of both side of cubicle, so as to ensure its uniformity in size and high mechanical strength. The cubicle will not be out of shape during loading & unloading, transportation, installation and operation.
The protection grade of enclosure is IP4X and that of the compartment is IP2X, so that , the three H.V. compartments are of full metal isolation and independently connect ground between each other and with the L.V. compartment, to ensure the safety of equipments and the personnel safety.
There is a metal shielding passage for the secondary cables crossing, to ensure that the high electric field inside the cubicle will not interfere with the working of the secondary control circuit.
The cubicle door is coated by plastic powder, so that the surface is anti-impact and corrosion-proof, and ensure a beautiful appearance.
Perfect internal anti arcing fault design. The pressure-releasing devices are respectively mounted on the top of handcart compartment, busbar compartment and cable compartment. When the internal fault arc occurs, the pressure releasing plate will be automatically opened to release the gas and pressure, so as to protect the near compartment from suffering and
ensure the safety of operators in front of the cubicle.
6.2 CB compartment
A special guide rail, which is II model of high strength, is installed in CB compartment for the handcart to move inside the compartment. The II model guide rail improves the reliability of the movable electricity joints between the CB handcart and the cubicle through the four-direct positioning against the circuit breaker. It is processed by the advanced laser cutting machine and its positioning is accuracy. The handcart can move between the isolating/testing position and the working
position. The movable baffle plate is made of good metal sheet is installed on the back wall of the handcart compartment. When the handcart moves from the isolating/testing position to the working position, the baffle plate will automatically open, contrarily, it will automatically close, thereby to protect the operators from touching the electricity.
All the normal operations of the switchgear including the opening/closing operation, the movement of the handcart between the isolating/testing position and the working position, and the operation of the earth switch, are done only if the cubicle door is closed. The closing/opening state of the CB handcart, the position of the CB handcart and the closing/opening state, are all equipped with the obvious and reliable mechanical indicators or the electronic analog indicators according to the requirement, so as to effectively ensure the personnel safety.
The coupling between the secondary circuit of the switchgear and that of the handcart is realized through the manual secondary aerial plug. Only when the handcart is in the isolating/test position, the secondary plug can be plugged into or unplugged. When the handcart is in the working position, the secondary plug will be locked and can not be unplugged due to the effect of the mechanical interlocking device.
6.3 Handcart
The frame of the handcart is made of the steel plate after bending and is welded together. According to its usage, the handcart can be sorted into CB handcart, PT handcart, disconnector handcart and so on. The height and depth of different kinds are same, so those of same specification are interchangable. The handcart has the isolating/testing position and the working position in the cubicle. Each position is equipped with a positioning device to ensure that the handcart only can be correspondingly operated in the specified position. Unlock the position lock before move the handcart, the circuit breaker must be in opening state before move the CB handcart.
6.4 Hydraulic lift type service truck
The service truck is lift type, which can easily lift the handcart or put it on the ground or the desk. There are the reliable locking devices: Only when the service truck reliably connect the cubicle, the handcart can be pushed into the cubicle or pulled out from the cubicle; When the handcart is pulled onto the service truck, it will be conveniently locked and the height will be suitably lower during transportation to avoid the accident of overturning.
6.5 Busbar compartment
The main busbar is supported by the insulator of high strength, the busbar between the cubicles is separated from each other through the busbar bushings, so as to limit the spread of internal fault arc. The busbar bushing is the new-style shielding one, which can effectively improve the electric field at the side sealing plate.
6.6 Cable compartment
In the cable compartment, there are current transformer, earth switch(with manual operating mechanism), over-voltage protector(The depth of the cubicle shall be 2800mm when the arrester is installed inside.), and several pieces of cables.
JN model earth switch has the short-circuit making ability, and has a quick closing mechanism, whose operation is independent of the main shaft, and the making speed of the switch and the produced torque are not controlled by the operating mechanism.
6.7 Mal-operation protection
The cubicle has reliable mal-operation protection function.
◆ Only when the circuit breaker is in opening position , the handcart can be pushed from the isolating/testing position to the working position, contrarily, it is same.
◆ Only when the CB handcart completely reaches the testing position or the working position, the circuit breaker will close.
◆ Only when the CB handcart completely reaches the testing/isolating position or the moving-out position, the earth switch will close.
◆ When the earth switch is in the closing position, the handcart can’t be pushed from the isolating/testing position to the working position.
◆ Only when the earth switch is in the closing state, the door of the cable compartment can be opened.
◆ When the handcart is in the working position, the secondary plug shall be locked and can’t be pulled out.

Fig.1 Section Drawing of Feeder Cubicle
A. Busbar compartment
D. Instrument compartment
1. Pressure releasing plate
4. Insulator
7. Current transformer
10. Fixed contact arm
13. Circuit breaker
16. Main busbar
B. CB compartment
E. Small busbar compartment
2. Cubicle body
5. Earth switch
8. Earth bar
11. Shutter mechanism
14. Secondary plug
17. Branch busbar
C. Cable compartment
3. Busbar bushing
6. Interphase insulation plate
9. Contact box
12. Guide rail
15. Pressure releasing plate of CB compartment
18. Pressure releasing plate of busbar compartment
FOUNDATION REFERENCE
All the construction of the cubicle’s installation foundation should accords with related provisions of “Technical Specifications
for Power Construction and Acceptance”.
Fig. 2 is the typical layout figure of KYH1-40.5 model switchgear for the designers reference. The detail dimensions ,
shall be adjusted according to the different cubicle style.
The width of the operating passage shall be over 2500mm for single row layout, the distance between the two rows shall
be over 3000mm for double row layout face to face.
The embedding of the foundation frame commonly adopts the double grouting method, and will be done by the electrical
installation unit after the construction.
The height of the channel steel shall be preserved with a wide margin together with the standard height of the foundation
while the construction design, and the anchoring steel plate shall be embedded on the foundation every a space of 1
1.5mm along the frame.
The level of the frame shall be calibrated when it is embedded, the required level error and flatness shall accord with
clause 2.0.1 of GB 50171 standard, in other words, the non-straightness per meter shall be less than 1mm and the total
length shall be less than 5mm, the levelness per meter shall be less than 1mm and the total length shall be less than 5mm,

Remarks: This sketch is for the standard incomimg/outgoing cubicle(1200 2600 2400), other scheme
can be adjusted according to this sketch, or consult the manufacturer.

Remarks: This sketch is for the standard incomimg/outgoing cubicle(1200 2600
2400), other scheme can be adjusted according to this sketch, or consult the manufacturer.
Fig.2 Sketch of Installation Foundation
the total length of the position error and non-parallelism shall be less than 5mm. Furthermore, The top height of foundation frame shall be less 3 5mm than the ground level of the distribution room.
ORDERING INSTRUCTIONS
The user shall provide the following technical documents as placing an order:
8.1 Primary single line diagram and circuit usage, rated voltage, rated current, rated short-circuit breaking current, the distribution room plan and cubicle arrangement diagram.
8.2 Model, specification and quantity of the main components in the cubicle. For example, if the cubicles shall be connected through the busbar bridge, the user shall provide the details data, such as rated current-carrying capacity of the busbar bridge, the span of the busbar bridge, height from the ground, phase sequence of incoming/outgoing and son on.
8.3 Measurement, control and protection functions of the cubicle, other requirements of lock-up and automation devices.
8.4 The specifications of incoming/outgoing cables.
8.5 Special service conditions shall be pointed out as ordering;
8.6 Other special requirements.
ATTACHED DOCUMENTS, ACCESSORIES AND SPARE PARTS
9.1 The attached documents includes:
◆ Qualification certificate and factory test report; ◆ Product Instruction;
◆ Secondary connection diagram;
◆ Packing list (including accessories, spare parts).
9.2 Accessories and spare parts:
◆ Forward handle for the CB handcart;
◆ Manual energy storage handle for the circuit breaker; ◆ Operating handle for the earth switch.
SPECIAL ATTENTIONS
The switchgear will be of high condensation danger if it operates in the site where it is of high humidity, big difference in temperature between the day and the night, and big variation of the temperature. So the heater must operate all day if the switchgear in the steady or operating state. However, the heater need not operate when the switchgear operates under the load current up to 1250A.
SINGLE LINE DIAGRAM(SLD)
Please find hereunder attached single line diagrams(SLD).
11.1 The models of the primary components listed in the sheet are for design selection, please consult the manufacturer if the user need other models.
11.2 For the single line diagram not listed in the sheet, please consult the manufacturer.
SLD NO. | 001 | 002 | 003 | 004 | 005 | |
Main Circuit Scheme | ||||||
Usage | Incoming/outgoing | |||||
Outer dimension(W | 1200 | 1200 | ||||
Rated current(A) | 630 | |||||
Main Components | VCB of VHY1-40.5 | 1 | 1 | 1 | 1 | 1 |
CT of LZZBJ18-35Q | 3 | 3 | 3 | 6 | 3 | |
Combinationover-voltageprotectiondevice | 1 | 1 | 1 | 1 | 1 | |
PT of JDZ9-35Q or JDZX9-35Q | ||||||
Fuse of XRNP-40.5/0.5 | ||||||
Earth switch of JN | 1 | |||||
Remarks | The power display is optional, the cubicle with the arrester shall be 2800mm deep. | |||||
SLD NO. | 006 | 007 | 008 | 009 | 010 | |
Main Circuit Scheme | ||||||
Usage | Incoming/outgoing | |||||
Outer dimension(W | 1200 | 1200 | ||||
Rated current(A) | 630 | |||||
Main Components | VCB of VHY1-40.5 | 1 | 1 | 1 | 1 | 1 |
CT of LZZBJ18-35Q | 6 | 3 | 3 | 3 | 3 | |
Combinationover-voltageprotectiondevice | 1 | 1 | 1 | 1 | 1 | |
PT of JDZ9-35Q or JDZX9-35Q | ||||||
Fuse of XRNP-40.5/0.5 | ||||||
Earth switch of JN | 1 | 1 | ||||
Remarks | The power display is optional, the cubicle with the arrester shall be 2800mm deep. |
SLD NO. | 011 | 012 | 013 | 014 | 015 | |
Main Circuit Scheme | ||||||
Usage | Incoming/outgoing | Busbarsectioncubicle | ||||
Outer dimension(W | 1200 | |||||
Rated current(A) | 630 | |||||
Main Components | VCB of VHY1-40.5 | 1 | 1 | 1 | 1 | 1 |
CT of LZZBJ18-35Q | 3 | 3 | 3 | 3 | 3 | |
Combinationover-voltageprotectiondevice | 1 | 1 | Optional | |||
PT of JDZ9-35Q or JDZX9-35Q | ||||||
Fuse of XRNP-40.5/0.5 | ||||||
Earth switch of JN | 1 | |||||
Remarks | The power display is optional, the cubicle with the arrester shall be 2800mm deep. | |||||
SLD NO. | 016 | 017 | 018 | 019 | 020 | |
Main Circuit Scheme | ||||||
Usage | Isolation | |||||
Outer dimension(W | 1200 | 1200 | ||||
Rated current(A) | 630 | |||||
Main Components | VCB of VHY1-40.5 | |||||
CT of LZZBJ18-35Q | 3 | 6 | 3 | 6 | ||
Combinationover-voltageprotectiondevice | Optional | Optional | Optional | Optional | Optional | |
PT of JDZ9-35Q or JDZX9-35Q | ||||||
Fuse of XRNP-40.5/0.5 | ||||||
Earth switch of JN | ||||||
Remarks | The power display is optional, the cubicle with the arrester shall be 2800mm deep. |
SLD NO. | 021 | 022 | 023 | 024 | 025 | |
Main Circuit Scheme | | | | | | |
Usage | Isolation | Lightening Arrester | Busbar uprise | |||
Outer dimension(W | 1200 | |||||
Rated current(A) | 630 | |||||
Main Components | VCB of VHY1-40.5 | |||||
CT of LZZBJ18-35Q | 3 | |||||
Combinationover-voltageprotectiondevice | 1 | HY5WZ 3 | HY5WZ 3 | 1 | Optional | |
PT of JDZ9-35Q or JDZX9-35Q | ||||||
Fuse of XRNP-40.5/0.5 | ||||||
Earth switch of JN | ||||||
Remarks | The power display is optional, the cubicle with the arrester shall be 2800mm deep. | |||||
SLD NO. | 026 | 027 | 028 | 029 | 030 | |
Main Circuit Scheme | ||||||
Usage | Busbar uprise | Measurement | PT | |||
Outer dimension(W | 1200 | |||||
Rated current(A) | 630 | |||||
Main Components | VCB of VHY1-40.5 | |||||
CT of LZZBJ18-35Q | 3 | 3 | ||||
Combinationover-voltageprotectiondevice | HY5WZ 3 | |||||
PT of JDZ9-35Q or JDZX9-35Q | 3 | JDZX11-35R 3 | JDZX11-35R 3 | JDZX11-35R 3 | ||
Fuse of XRNP-40.5/0.5 | 3 | 3 | 3 | 3 | ||
Earth switch of JN | ||||||
Remarks | The power display is optional, the cubicle with the arrester shall be 2800mm deep. |
SLD NO. | 031 | 032 | 033 | 034 | 035 | |
Main Circuit Scheme | ||||||
Usage | PT | PT+incoming/outgoing | Earth switch | |||
Outer dimension(W | 1200 | |||||
Rated current(A) | 630 | |||||
Main Components | VCB of VHY1-40.5 | |||||
CT of LZZBJ18-35Q | 3 | |||||
Combinationover-voltageprotectiondevice | ||||||
PT of JDZ9-35Q or JDZX9-35Q | 3 | 3 | JDZX11-35R 3 | JDZX11-35R 3 | ||
Fuse of XRNP-40.5/0.5 | 3 | 3 | 3 | 3 | ||
Earth switch of JN | Earth switch 1 | |||||
Remarks | The power display is optional, the cubicle with the arrester shall be 2800mm deep. | |||||
SLD NO. | 036 | 037 | 038 | 039 | 040 | |
Main Circuit Scheme | ||||||
Usage | PT + Busbar uprise | Transformer | ||||
Outer dimension(W | 1200 | |||||
Rated current(A) | 630 | 50 | ||||
Main Components | VCB of VHY1-40.5 | |||||
CT of LZZBJ18-35Q | ||||||
Combinationover-voltageprotectiondevice | ||||||
PT of JDZ9-35Q or JDZX9-35Q | JDZX11-35R 3 | 3 | ||||
Fuse of XRNP-40.5/0.5 | 3 | 3 | 3 | |||
Earth switch of JN | ||||||
Remarks | The power display is optional, the transformer cubicle shall be separated, the fuse link shall be equipped according to the capacity. |