electrisity control box
solar power control panel

Summary

HXGN11-12 HV Switchgear Metal-clad AC Ring Main Unit(RMU) is a new HV  apparatus which is introduced from aboard and accords with the requirements  of rural and city power distribution & transmission system. This product has     passed the type test report and all the performances have already satisfied the requirements of IEC 62271-200 Standard <<1KV-52KV AC HV Metal-clad  Switchgear and its Controlling Equipments>>. It has reliable anti-misoperation  function, and the protection degree is IP3X. It applies to the 12kV, three phases, 50/60Hz power distribution systems in such occasions: Enterprises, Mining  places, High buildings, Residence community, School, Park, etc.

Ambient condition

  • Ambient temperature: -10℃ ~+40℃;
  • Altitude: ≤1000m;
  • Relative humidity:  ≤90%(Month mean value);≤ 95%(+25℃ )(Daily mean value);
  • Occasions without flammable and explosive matter, without corrosive chemical and frequent severe vibration, without strong shake.

Model

Model

Product feature

The meter’s compartment is insulated by metal partitions board from the main busbar compartment and others, so it is saftelyfor usage.

Set metal partitions board with in the disconnect gaps, and it is intergrated with earthing swit ch: when the eart hing switc h isclosed, it is disconnecting the isolating gaps, so it is very reliable, safety and easily for maintanence;

Spring energy storage operating: when the HV fuses blew, all the three phases will shed automatically;

The mechanical interlock satisfy the ‘5 protection’ requirements.

The switchgear can be as RMU power supply unit or other connection types very easily, and it is also can be extended very easily;

Use the vacuum load break for breaking and closing, so it is reliable and safety.

The structure of the switchgear is simple, it has beautiful appearance, and can be operated easily by both manual and motor.

Technical specification

No .ItemUnitParameter
1Rated voltagekV12
2Rated frequencyHz50
3Main busbar rated currentA630
4Rated short-time withstand current( Functional unit)kA/S20/3
5Earthing circuit rated short time withstand currentkA20/2
6Rated peak withstand currentkA50
7Earthing circuit rated peak withstand currentkA50
8Main/earthing circuit rated short circuit making current(Peak)kA50
9Fuse breaking currentkA31.5
10Mechanical lifeTimes5000
111 min P.F withstand voltagekA42/48
P to E, P to P/ Across  open contacts (Valid value )
12Lightning impulse withstand voltagekA75/85
P to E, P to P/ Across  open contacts (Peak value )
13Secondary circuit 1 min P.F. withstand voltagekA2
14Outline dimension(WxDxH)mm650x850x1900
15Net weightKg160
16Package outline dimension(WxDxH)mm800x1000x2000
17Gross weightKg220

Outline and dimension

HXGN11-12 HV Switchgear Metal-clad AC Ring Main Unit(Feeder)

HXGN11-12 HV Switchgear Metal-clad AC Ring Main Unit(Feeder)

1. Insulation insert board    2. Anti-explosion abservation window    3. Primary cable buck

4. Dry type CT    5. Operation mechanism     6. LBS and fuse combination apparatus

7. Main busbar compartment    8. Busbar bushing    9. Press releasing device.