electrisity control box
solar power control panel

Summary

HXGN15-12L  HV switchgear metal enclosed AC ring main unit is a new HV  apparatus which introduced from abroad and accord with the requirement of rural distribution and city distribution in nation. Main switch, operation mechanism and component use the SFL-12 model  SF6 switch equipment  produced by ABB company or FLN36-12D model SF6 switch equipment produced by our company. Also can use the HAD/US model SF6 circuit breaker or VD4-S model vacuum circuit breaker produced by company ABB according to requirement of customer operation type is manual and motor.

Ambient condition

  • Ambient temperature: -25℃ ~+40℃;
  • Altitude: ≦1000m;
  • Relative humidity: daily average ≤ 95%, monthly average ≤ 90%;
  • Occasions without flammable and explosive matter, without corrosive chemical and frequent severe vibration, without strong shake.

Model

MOdel

Product feature

Panel structure: The panel body is enclosed by 2 mm aluminium-zinc plated steel plate after multi-bending. It is simple, firm, delicate and peculiar.

1. Busbar compartment

The busbar compartment is located in the top and connect with neighboring panel.

2. Load break switch is a separated unit with SF6 gas.

3. Cable compartment

Approximate 75% room for connecting cable and installing fuse, earthing switch and PT.

4. Mechanism chamber and interlock

The chamber consists of operating mechanism, mechanism interlock, position indicator, auxiliary contact trip coil, power indicator and interlock.

5. LV chamber

LV compartment is located in the top. It mainly user for installing instrument, relay and motor.

6. Circuit breaker compartment

The circuit breaker (SF6 or Vacuum) is located below load break switch.

 Pressure release:

A. Upper pressure release

It is mainly used for releasing gas pressure which produced by arc accident in busbar load break switch compartment.

B. Down pressure release

It is mainly used for releasing gas pressure which produced by arc accident in cable small compartment.

Technical specification

ItemUnitParameter
Rated voltagekV10
Highest working voltagekV12
Rated frequencyHz50/60
Main busbar rated currentA630
Main loop, earthing loop rated short time withstand currentkA/s20/3
Main loop, earthing loop rated peak withstand currentkA50
Main loop, earthing loop rated short circuit making currentkA50
Load break switch full capacity breaking timeTimes100
Fuse breaking current 31.5-50
Mechanical lifeTimes2000
Rated transfer currentA1700
1min P.F. Withstand(virtral value),phase to phase, earth/across open contactskV42/48
Lightning impulse withstand voltage(peak)    phase to phase, earth/across open contactskV75/85
Secondary loop 1min P.F. WithstandkV2
Protection degree IP3X

Outline and dimension

XGN(W)74-12 series consisting of bottom compartment, gas compartment, operating mechanism, interlock mechanism and LV control compartment. Each compartment disconnected by copper plate. Gas compartment have pressure release device. Lower compartment have pressure release guide in order to avoid accident. Degree of protection is IP3X.

Width of circuit breaker panelmm750
Other width of panelmm375/500
Heightmm1600/1850
Depthmm980
Height of LV casemm450

Outline and dimension