factory control panel
Power General panel

Summary

VS1(ZN63A)-12/24 Model indoor AChigh voltage vacuum circ uit breaker isatype of holistic and completelysealed HV switchgear,it has compactabledimensionand small volume.The VCB applies to power system of ratedvoltage 12kV,three-phase andAC50/60Hz.It is applicable in occasions withfrequent operations,acting to protect and control line and electric appar atus.The product conformsto IEC62271,GB1984,JB3855 and DL1403 and pasesKEMA test.

Ambient condition

  • Altitude: 1000m;
  • Ambient temperature: -25 ~+40 ;
  • Relative humidity: daily average 95 , monthly average 90 ;
  • Earthquake intensity: 8 degree;
  • Applicable occasions should free from inflammables, explosives, corrosives and severe vibration.

Model

factory control panel
Power General panel

Product feature

1. Holistic structure

2. Sealed spark chamber

3. Effective vacuum arc-extinguish

4. Good mechanical behavior

5. Various mounting approach

Technical specification

No.ltemUnitData
1Rated voltagekV12/24
2Rated frequencyHz50/60
3Rated currentA  630,1000,125016002000,2500,31504000
4Rated short-circuit breaking currentkA202531.531.5404050
5Rated short-circuit making currentkA50638080100100125
6Rated short-time withstand currentkA202531.531.5404050
7Rated peak withstand currentkA50638080100100125
8Rated pull-out breaking currentkA  12.612.6161620
9Rated out-of-phase earthing fault breaking currentkA17.421.727.427.434.734.743.5
10Rated short-circuit breaking current breaking timeTimes50303012
11Rated operation sequence O-0.3s-CO-180s-COO-180s-CO-180s-CO
12Rated breaking current of single capacitor bankA630
13Rated breaking current of back to back capacitor bankA400
141min.PF withstand voltagekVPhase to phase/to earth:42,across open contacts:48
15Lightning impulse withstand voltagekVPhase to phase/to earth:75,acrossopen contacts:85
16Mechanical lifeTimes20000
17Closing timems≤75
18Opening timems≤60
19Power storage time under rated voltageS≤10

Product structure

factory control panel
Power General panel
factory control panel
Power General panel

Diagram 1 Outline dimension of handcart type VS1 applies to 800mm width panel

Ratedcurrent(A)6301000125016002000250031504000
Rated short-circuit
breaking current(kA)
2,02520,25,31.520,25,31.531.531.5,4031.5,40404050
Size of static contact (mm)φ35φ35φ49φ55φ79φ109φ109φ109

factory control panel
Power General panel

Diagram 2 Outline dimension of fixed type VS1 applied to 800mm width panel

Note: the size inside bracket is applied to1000mm width panel; rated current: 2000A~4000A.

Rated current (A)6301000125016002000250031504000
Rated short-circuit
breaking current(kA)
202520,25,31.520,25,31.531.531.5,4031.5,40404050